  • 36kv Heat Shrink Termination Kit Indoor Terminal Cable Accessories
  • 36kv Heat Shrink Termination Kit Indoor Terminal Cable Accessories
  • 36kv Heat Shrink Termination Kit Indoor Terminal Cable Accessories
  • 36kv Heat Shrink Termination Kit Indoor Terminal Cable Accessories
  • 36kv Heat Shrink Termination Kit Indoor Terminal Cable Accessories
  • 36kv Heat Shrink Termination Kit Indoor Terminal Cable Accessories
Find Similar Products

Basic Info.

Model NO.
NRS
Transport Package
Carton
Trademark
CYG
Origin
China
HS Code
8547200000

Product Description

4E-NRS, 4E-WRS, 4E-JRS Heat Shrinkable Cable Accessories
4E-NRS, 4E-WRS, 4E-JRS heat shrinkable cable accessories is applied to 35kV and below rubber cable. Heat shrinkable cable accessories is using import multi-phase polymer, it's the update products of wrapped type cable accessories. With convenient installation, keep on suitable radial pressure on the cable body, interface characteristic is good. the parameter type stress control tube to improve the distribution of the electric field, which can effectively solve the cable outer shield section in electric stress concentration problem. The electrical properties are improved from wrapped type cable accessories to ensure the safety and reliable operation. The main components are tubular, basically including stress tube, insulation tube, three fingered tube, sealed tube protective sleeve, etc
   
Main performance and structure features:
Technical performance: meet BS EN 50181, IEC60502, GB/T12706 requirements.
Heat shrinkable raw materials: stress tube is parameter type, well-distributed electric field at the insulating cable cut off place. Insulating tube has insulation effect, protective sleeve has protection effect. Product heat shrinkable is quite stable, can shrinkable to the original size in heating condition, the residual deformation is small. All the products are processing forming in the factory. There's no need to use fire, no special training, installation is simple and fast.
It has resistance to filth, aging, and good waterproof, with superior cold heat resistant performance.
Surface is smooth and beautiful.

Heat shrinkable outdoor termination

36kv Heat Shrink Termination Kit Indoor Terminal Cable Accessories
1. Lug  2. Cable core  3.  Melt adhesive  4. Sealing tube  5. Cable insulation layer  6. Heat shrinkable tube  7. Single hole rain skirt  8. Stress tube  9. Cable semi-conductive layer  10. Copper copper screen layer  11. Three hole rain skirt  12. Three fingered tube  13. Earthing wire  14. Cable  15. Triangulation cone
 
Voltage
Section number
1 2 3 4
8.7/15 25-50 70-120 150-240 300-400
12/20, 26/35 50-95 120-185 240-400 500-630

Heat shrinkable indoor termination

36kv Heat Shrink Termination Kit Indoor Terminal Cable Accessories
1. Lug  2. Cable core  3.  Melt adhesive  4. Sealing tube  5. Cable insulation layer  6. Heat shrinkable tube  7. Single hole rain skirt  8. Stress tube  9. Cable semi-conductive layer  10. Copper copper screen layer  11. Three hole rain skirt  12. Trigeminal sheath  13. Earthing wire  14. Cable  15. Triangulation cone
 
Voltage
Section number
1 2 3 4
8.7/15 25-50 70-120 150-240 300-400
12/20, 26/35 50-95 120-185 240-400 500-630

Heat shrinkable middle joint

36kv Heat Shrink Termination Kit Indoor Terminal Cable Accessories
 1. Semi conductive tape  2. Waterproof sealant adhesive  3. Semi conductive tube  4. Cable insulation  5. Connecting tube  6. Semi conductive tape  7. Semi conductive layer  8. Outer insulation tube  9. Inner insulating tube  10. Stress tube 11. Copper screen tape
 
Voltage
Section number
1 2 3 4
8.7/15 25-50 70-120 150-240 300-400
12/20, 26/35 50-95 120-185 240-400 500-630

Heat shrinkable indoor, outdoor termination, and joint electrical performance parameters
Item Requirement
8.7/15 (17.5) 12/20 (24) 26/35 (40.5)
5min Power frequency voltage test 39kV, no flashover, no breakdown 54kV, no flashover, no breakdown 117kV, no flashover, no breakdown
Partial discharge test 15kV discharge capacity≤10pC 20kV discharge capacity≤10pC 45kV discharge capacity≤10pC
Lightning impulse test 95kV 125kV 200kV
10 times of positive and negative, no flashover, no breakdown
Constant voltage load cycle test in air 22kV 30kV 65kV
The conductor is heated to 95-100ºC, each cycle is 8h, heating 5h and cooling 3H for 60 cycles.
Partial discharge test at high temperature 15kV discharge capacity≤10pC 20kV discharge capacity≤10pC 45kV discharge capacity≤10pC
15min AC voltage withstand test 22kV, no flashover, no breakdown 30kV, no flashover, no breakdown 65kV, no flashover, no breakdown
Negative DC voltage test 52kV, no flashover, no breakdown 64kV, no flashover, no breakdown 156kV, no flashover, no breakdown
4H power frequency voltage test 35kV, no flashover, no breakdown 48kV, no flashover, no breakdown 104kV, no flashover, no breakdown
Outdoor termination salt spray test 1000h 11kV, no flashover, no breakdown 15kV, no flashover, no breakdown 32.5kV, no flashover, no breakdown
Indoor termination humidity test 300h 11kV, no flashover, no breakdown 15kV, no flashover, no breakdown 32.5kV, no flashover, no breakdown