Customization: | Available |
---|---|
Application: | Construction, Overhead, Underground, Industrial, Power Station, Telecommunication |
Voltage: | Low and Medium Voltage Cable |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Jiangsu Dongfeng Cable Co.,Ltd(Originally Wuxi Dongfeng Factory )was founded in 1988,which is an high-tech private enterprise with collection of research,development and production of various wires and cables.The registered capital is 308 million RMB,total asset is 1810 million RMB.Factory area covers 160 thousand square meters,of which construction area is 120 thousand square meters.The corporation owns a Technology Center of Jiangsu Province Level.
Main products of the corporation are :500Kv extra high voltage cable,220 and 110kV and 60kV high voltage power cable,XLPE insulated power cable for rated voltage from 1kV to 35kV,PVC insulated power cable,aerial insulation cable,aerial insulation cable,cables for electrical equipments ,low-smoke halogen-free flame retardant cable,fire proof cable,fire proof cable,general rubber cable,mineral cable,welding cable,control cable,AAC and ACSR,etc.
6) Metallic Armor
The armor, if required, consists of single layer of round wires or double tapes of galvanized steel or aluminum or other non-magnetic metals. Single core cables are normally armored with aluminum(other non-magnetic metals), because non-magnetic armor is essential for single core cable for use on A.C circuit .
7) Outer Sheath
All cable are normally provided with an extruded PVC out sheath, black colored(class ST2). Other materials can be available upon request,as PE , polyethylene,high flame or fire retardant PVC and etc.
8) Core Identification
The multiple conductors are identified as according IEC60502 .
power cable,pvc cable,abc cable,conductor,cable,wiring cable,electric wire,acsr ,flexible cable,spiral cable,power supply cable,copper wire,pvc wire cable,wire cable
The following information are indicated on the surface of the outer sheath. However, the marking can also be customized.
----voltage rating, area for cable
----manufacturer's name
----year of manufacturer
----lengther for cable
----etc
The finished cables meet all the appropriate test requirments specified in IEC60502.
Items | Test Requirements | ||||||
Routine test |
1.Resistance of conductors | Reference page 12 | |||||
2.Partial discharge test | 3.6/6(7.2)KV-18/30(36)KV: Not more than 20pC at 1.5Uo | ||||||
3.Power frequency voltage test | 0.6/1KV-3.6/6(7.2)KV: (2.5Uo+2)KV/5min 6/10(12)KV-18/30(36)KV: (2.5Uo)KV/5min |
||||||
Special test |
1.Conductor examination | ||||||
2.Check of dimension | |||||||
3. Voltage test for 4h | 6/10(12)KV-18/30(36)KV: 3UoKV/4h | ||||||
4. Hot set test |
Item | Requirements | |||||
Temperature (±3°C) | 200 | ||||||
Time under load(Min.) | 15 | ||||||
Stress (N/cm2) | 20 | ||||||
Max. elongation under load (%) | 175 | ||||||
Max. permanent elongation after cooling (%) | 15 | ||||||
Type test |
1.Partial discharge test | 3.6/6(7.2)KV-18/30(36)KV: Not more than 20pC at 1.5Uo | |||||
2.Heating cycle test | 3.6/6(7.2)KV-18/30(36)KV Conductor temperature: 100°C 3 times (On 2h+Off 4h) |
||||||
3.Impulse withstand test |
Rated voltage (kV) |
3.6/6(7.2) | 6/10(12) | 8.7/15(17.5) | 12/20(24) | 18/30(36) | |
Test voltage (kV) |
60 | 75 | 95 | 125 | 170 | ||
Each ±10 shots at 95°C A.C. voltage test after impulse withstand test 3.6/6(7.2)KV: (2.5Uo+2)KV/15min. 6/10(12)KV-18/30(36)KV: (2.5Uo)KV/15min. |
|||||||
4.High-voltage test for 4h | 3.6/6(7.2)KV-18/30(36)KV: 3UoKV/4h |